Performance
In a single pass through the purifier at a full flow rate:
Water Removal: From 50 ppm down to less than 5 ppm in a single pass & down to 3 ppm after two passes. (According to the PPM Tester)
Gas Removal: From fully saturated with air (10% to 12% by volume) down to less than 0.1% by volume.
Particulate Matter Removal: 98% of particles over 0.5mm or over 1 mm or over 5mm at customers preference.
Dielectric Strength: Improve dielectric strength up to 75-80KV for New oil.
Acid Removal: after treatment, the acid value will down to less than 0.1mgKOH/g
Free Carbon Removal: there is no free carbon’s residue
Oil Regeneration Machine's Technical Parameters
Parameters
|
Unit
|
ZYD-I-30
|
ZYD-I-50
|
ZYD-I-100
|
ZYD-I-150
|
ZYD-I-200
|
ZYD-I-250
|
ZYD-I-300
|
Flow
|
L/min
|
30
|
50
|
100
|
150
|
200
|
250
|
300
|
Working vacuum
|
MPa
|
0.08 ~ 0.099
|
Working Pressure
|
MPa
|
≤0.4
|
Temperature Range
|
℃
|
20 ~ 80
|
Power
|
|
Three Phase 50HZ380V(as per the customer’s requirements)
|
Working Noise
|
dB(A)
|
75
|
75
|
75
|
80
|
80
|
80
|
80
|
Heating Power
|
kW
|
30
|
40
|
60
|
90
|
120
|
150
|
180
|
Total Power
|
kW
|
35.5
|
41.5
|
62.5
|
95.5
|
128.5
|
159.5
|
192
|
Inlet/Outlet
|
mm
|
φ25
|
φ32
|
φ42
|
φ50
|
φ50
|
φ60
|
φ60
|
Weight
|
kg
|
400
|
550
|
800
|
950
|
1100
|
1300
|
1600
|
Overall
|
Length
|
mm
|
1350
|
1480
|
1850
|
1950
|
2100
|
2150
|
2250
|
Width
|
mm
|
1320
|
1450
|
1810
|
1900
|
2000
|
2100
|
2200
|
Height
|
mm
|
1350
|
1460
|
1860
|
1930
|
2150
|
2200
|
2300
|
Contact information
Sky ZHOU
Email: sky8tears@gmail.com
Tel/whatsapp +8618523178237
Website:www.assenpe.com